Battery backup time calculator and tables

How long an inverter battery lasts at your load, for every common Ah size, tubular and lithium. Worked out with the same engine as our inverter calculator.

  • Calibrated to manufacturers’ published backup tables
  • 12 V and 24 V banks
  • Lithium (LiFePO4) too

Backup time by battery size

One 12 V tubular battery on a home inverter. 100 W is a fan and four lights; 400 W is three fans, six lights, a TV and Wi-Fi.

Battery (12 V tubular)100 W200 W300 W400 W500 W
100 Ah9 h 30 min4 h 05 min2 h 20 min1 h 25 min1 h 05 min
120 Ah11 h 30 min5 h 10 min3 h2 h1 h 20 min
135 Ah13 h6 h3 h 35 min2 h 25 min1 h 35 min
150 Ah14 h 25 min6 h 50 min4 h 05 min2 h 50 min2 h
160 Ah15 h 25 min7 h 20 min4 h 30 min3 h2 h 10 min
165 Ah15 h 50 min7 h 35 min4 h 40 min3 h 10 min2 h 20 min
180 Ah17 h 20 min8 h 25 min5 h 10 min3 h 35 min2 h 35 min
200 Ah19 h 10 min9 h 30 min5 h 55 min4 h 05 min3 h
220 Ah21 h 05 min10 h 35 min6 h 35 min4 h 40 min3 h 30 min
230 Ah22 h 05 min11 h7 h4 h 55 min3 h 40 min
250 Ah24 h12 h7 h 40 min5 h 30 min4 h 05 min
260 Ah25 h12 h 30 min8 h 05 min5 h 40 min4 h 20 min

Lithium (LiFePO4) batteries

Using 80% of the stored energy, the depth of discharge in Loom Solar’s LiFePO4 datasheet, and 80% inverter efficiency.

Lithium battery100 W200 W300 W400 W500 W
12.8 V 100 Ah lithium8 h 10 min4 h 05 min2 h 40 min2 h1 h 35 min
25.6 V 100 Ah lithium16 h 25 min8 h 10 min5 h 30 min4 h 05 min3 h 20 min
51.2 V 100 Ah lithium32 h 50 min16 h 25 min10 h 55 min8 h 10 min6 h 35 min
51.2 V 200 Ah lithium65 h 30 min32 h 50 min21 h 50 min16 h 25 min13 h 05 min

Battery backup questions

How do I work out battery backup time?

Multiply the battery voltage by its Ah to get watt-hours, take off inverter losses, and divide by the load in watts. Lead-acid gives less than its label at higher loads, so the tables here use a curve fitted to manufacturers’ published backup tables instead of the label alone.

Why is my backup shorter than the label suggests?

Inverter batteries are rated at C20, a 20-hour discharge. A typical home load drains them much faster than that, and lead-acid delivers less of its capacity at higher current. Ageing, heat and an inverter that cuts off early shorten it further.

Does a 24 V inverter give more backup?

Two 12 V batteries in series make 24 V and roughly double the stored energy, so at the same load the backup roughly doubles. Each battery also discharges at a lower current, which helps lead-acid a little more.

How accurate are these figures?

For 150 to 250 Ah tubular batteries they match Exide’s published Inva Zen backup tables within about 10% at 200 to 400 W. At very light loads (100 W) our figures are lower than Exide’s, so treat them as a safe minimum.