165 Ah battery backup time

How long a 12 V 165 Ah tubular inverter battery runs at different loads, alone and as a 24 V pair.

  • About 7 h 35 min at 200 W
  • About 3 h 10 min at 400 W

One 165 Ah battery (12 V inverter)

A fully charged, healthy battery. At 400 W it discharges at about 0.25C, against the C20 (0.05C) its Ah is rated at, so it gives less than the label.

LoadBackupExample
50 W31 h 40 minWi-Fi and two lights
100 W15 h 50 minA fan and three lights
150 W10 h 35 min
200 W7 h 35 minTwo fans, four lights, TV
250 W5 h 50 min
300 W4 h 40 minThree fans, lights, TV, Wi-Fi
400 W3 h 10 minThree fans, six lights, TV, Wi-Fi
500 W2 h 20 minAdd the fridge
600 W1 h 40 minFour fans, lights, TV, fridge
800 W1 h 05 minA big house, or a cooler

Two 165 Ah batteries (24 V inverter)

The usual set-up for 1.5 kVA and 2 kVA inverters.

LoadBackup (2 batteries, 24 V)
300 W10 h 35 min
400 W7 h 35 min
500 W5 h 50 min
600 W4 h 40 min
800 W3 h 10 min
1000 W2 h 20 min
1200 W1 h 40 min
1500 W1 h 10 min

165 Ah models we list

Specs as stated on each manufacturer’s page. Sorted by brand; we don’t rank them.

ModelTypeWarrantyMaker’s backup at 400 W
Exide FEM0-IMTT1650tall tubularNot stated—

Method: watt-hours at 12 V × the share lead-acid delivers at that current, fitted to V-Guard’s published 400 W backup table, ÷ load. Checked against Exide’s Inva Zen tables, which it matches within about 10% from 200 to 400 W and undershoots at 100 W. Real backup falls as the battery ages.