100 Ah battery backup time

How long a 12 V 100 Ah tubular inverter battery runs at different loads, alone and as a 24 V pair.

  • About 4 h 05 min at 200 W
  • About 1 h 25 min at 400 W

One 100 Ah battery (12 V inverter)

A fully charged, healthy battery. At 400 W it discharges at about 0.42C, against the C20 (0.05C) its Ah is rated at, so it gives less than the label.

LoadBackupExample
50 W19 h 10 minWi-Fi and two lights
100 W9 h 30 minA fan and three lights
150 W5 h 55 min
200 W4 h 05 minTwo fans, four lights, TV
250 W3 h
300 W2 h 20 minThree fans, lights, TV, Wi-Fi
400 W1 h 25 minThree fans, six lights, TV, Wi-Fi
500 W1 h 05 minAdd the fridge
600 W55 minFour fans, lights, TV, fridge
800 W40 minA big house, or a cooler

Two 100 Ah batteries (24 V inverter)

The usual set-up for 1.5 kVA and 2 kVA inverters.

LoadBackup (2 batteries, 24 V)
300 W5 h 55 min
400 W4 h 05 min
500 W3 h
600 W2 h 20 min
800 W1 h 25 min
1000 W1 h 05 min
1200 W55 min
1500 W40 min

100 Ah models we list

Specs as stated on each manufacturer’s page. Sorted by brand; we don’t rank them.

ModelTypeWarrantyMaker’s backup at 400 W
Exide FEM1-IMST1000short tubularNot stated—
Exide FEP0-IPST1000short tubularNot stated—
Exide IZST1000short tubular48 months (24 free replacement + 24 pro-rata)1 h 30 min
Livguard IT1048STshort tubular48 months (24 free replacement + 24 pro-rata)—

Method: watt-hours at 12 V × the share lead-acid delivers at that current, fitted to V-Guard’s published 400 W backup table, ÷ load. Checked against Exide’s Inva Zen tables, which it matches within about 10% from 200 to 400 W and undershoots at 100 W. Real backup falls as the battery ages.