ebbillcalc

135 Ah battery backup time

How long a 12 V 135 Ah tubular inverter battery runs at different loads, alone and as a 24 V pair.

  • About 6 h at 200 W
  • About 2 h 25 min at 400 W

One 135 Ah battery (12 V inverter)

A fully charged, healthy battery. At 400 W it discharges at about 0.31C, against the C20 (0.05C) its Ah is rated at, so it gives less than the label.

LoadBackupExample
50 W25 h 55 minWi-Fi and two lights
100 W13 hA fan and three lights
150 W8 h 25 min
200 W6 hTwo fans, four lights, TV
250 W4 h 30 min
300 W3 h 35 minThree fans, lights, TV, Wi-Fi
400 W2 h 25 minThree fans, six lights, TV, Wi-Fi
500 W1 h 35 minAdd the fridge
600 W1 h 10 minFour fans, lights, TV, fridge
800 W55 minA big house, or a cooler

Two 135 Ah batteries (24 V inverter)

The usual set-up for 1.5 kVA and 2 kVA inverters.

LoadBackup (2 batteries, 24 V)
300 W8 h 25 min
400 W6 h
500 W4 h 30 min
600 W3 h 35 min
800 W2 h 25 min
1000 W1 h 35 min
1200 W1 h 10 min
1500 W1 h

135 Ah models we list

Specs as stated on each manufacturer’s page. Sorted by brand; we don’t rank them.

ModelTypeWarrantyMaker’s backup at 400 W
Exide FEM1-IMST1350short tubularNot stated—
Exide FEP0-IPST1350short tubularNot stated—
Exide IZST1350short tubular48 months (24 free replacement + 24 pro-rata)2 h 25 min

Method: watt-hours at 12 V × the share lead-acid delivers at that current, fitted to V-Guard’s published 400 W backup table, ÷ load. Checked against Exide’s Inva Zen tables, which it matches within about 10% from 200 to 400 W and undershoots at 100 W. Real backup falls as the battery ages.